Marin County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5128 Mill Creek Ct

Approved

Filed Jun 18, 2026 by Morgan Pruitt, Valley Backflow Testing · filed from phone

Report

Date of service
Jun 18, 2026
Assembly type
RP
Serial number
K111870
Size
1
Test gauge serial
G-9822
Gauge calibration date
Nov 24, 2025
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Relief valve opened at
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-93-01071
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5128 Mill Creek Ct
Owner: Alex Ramirez
Parcel 041-93-01071