← Backflow review queue
Backflow assembly test · Hilltop Diner
ApprovedFiled Jul 9, 2025 by Shawn Nguyen, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 9, 2025
- Assembly type
- RP
- Serial number
- K929962
- Size
- 2
- Test gauge serial
- G-9500
- Gauge calibration date
- Dec 28, 2024
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 051-78-01015
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4779 Cedar Hollow Ct
Owner: Ramirez Holdings LLC
Parcel 051-78-01015