Mono County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Two Rivers Animal Hospital

Approved

Filed Jul 1, 2023 by Shawn Nguyen, Valley Plumbing & Backflow · filed from phone

Report

Date of service
Jul 1, 2023
Assembly type
RP
Serial number
Z432179
Size
2
Test gauge serial
G-2790
Gauge calibration date
May 21, 2023
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 051-62-01299
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4357 Sycamore Dr
Owner: Stroud Holdings LLC
Parcel 051-62-01299