Backflow assembly test · Maple Leaf Taqueria
ApprovedFiled Aug 6, 2023 by Shawn Nguyen, Valley Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Aug 6, 2023
- Assembly type
- DC
- Serial number
- B631002
- Size
- 2
- Test gauge serial
- G-3892
- Gauge calibration date
- Jun 16, 2023
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 051-90-01267
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.