← Backflow review queue
Backflow assembly test · Maple Leaf Taqueria
ApprovedFiled Jul 25, 2025 by Shawn Nguyen, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 25, 2025
- Assembly type
- DC
- Serial number
- B631002
- Size
- 2
- Test gauge serial
- G-4202
- Gauge calibration date
- Oct 21, 2024
- Check valve 1
- 3.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 051-90-01267
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3321 Quarry Rd
Owner: Okafor Holdings LLC
Parcel 051-90-01267