Backflow assembly test · Crossroads Taqueria

Approved

Filed Jun 2, 2024 by Shawn Nguyen, Valley Plumbing & Backflow · filed from phone

Report

Date of service
Jun 2, 2024
Assembly type
RP
Serial number
A769792
Size
4
Test gauge serial
G-5247
Gauge calibration date
Nov 22, 2023
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 051-94-01161
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7394 Ridgeview Ct
Owner: Whitcomb Holdings LLC
Parcel 051-94-01161