← Backflow review queue
Backflow assembly test · Crossroads Taqueria
ApprovedFiled Jul 7, 2025 by Avery Ramirez, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Jul 7, 2025
- Assembly type
- RP
- Serial number
- A769792
- Size
- 4
- Test gauge serial
- G-1427
- Gauge calibration date
- Oct 4, 2024
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 051-94-01161
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7394 Ridgeview Ct
Owner: Whitcomb Holdings LLC
Parcel 051-94-01161