Mono County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Crossroads Taqueria

Approved

Filed Jul 7, 2025 by Avery Ramirez, Heritage Backflow Testing · filed from phone

Report

Date of service
Jul 7, 2025
Assembly type
RP
Serial number
A769792
Size
4
Test gauge serial
G-1427
Gauge calibration date
Oct 4, 2024
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 051-94-01161
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7394 Ridgeview Ct
Owner: Whitcomb Holdings LLC
Parcel 051-94-01161