Monterey County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Bakery

Approved

Filed Aug 13, 2025 by Rowan Benton, Summit Plumbing & Backflow · filed from phone

Report

Date of service
Aug 13, 2025
Assembly type
RP
Serial number
A199137
Size
4
Test gauge serial
G-8674
Gauge calibration date
May 28, 2025
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 053-53-01077
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1836 Orchard Dr
Owner: Calloway Holdings LLC
Parcel 053-53-01077