Backflow assembly test · 6915 Pine Knoll Way
ApprovedFiled Apr 21, 2026 by Cameron Kessler, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Apr 21, 2026
- Assembly type
- DC
- Serial number
- A692521
- Size
- 3/4
- Test gauge serial
- G-2375
- Gauge calibration date
- Sep 10, 2025
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 053-28-01037
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
6915 Pine Knoll Way
Owner: Casey Danner
Parcel 053-28-01037