Backflow assembly test · 7185 Turkey Hill Rd

Approved

Filed Oct 12, 2024 by Parker Fairley, Patriot Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Oct 12, 2024
Assembly type
RP
Serial number
W106991
Size
3/4
Test gauge serial
G-5556
Gauge calibration date
Apr 26, 2024
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 053-33-01272
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.