Backflow assembly test · 2017 Quarry Dr
ApprovedFiled Mar 23, 2025 by Parker Brandt, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Mar 23, 2025
- Assembly type
- RP
- Serial number
- A825306
- Size
- 3/4
- Test gauge serial
- G-2114
- Gauge calibration date
- Jun 20, 2024
- Check valve 1
- 3.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 055-88-01154
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2017 Quarry Dr
Owner: Blake Calloway
Parcel 055-88-01154