← Backflow review queue
Backflow assembly test · 1194 Ridgeview Trl
ApprovedFiled Jan 9, 2026 by Cameron Ellery, Northstar Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Jan 9, 2026
- Assembly type
- RP
- Serial number
- K651876
- Size
- 1
- Test gauge serial
- G-8231
- Gauge calibration date
- Jul 22, 2025
- Check valve 1
- 3.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 055-32-01147
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
1194 Ridgeview Trl
Owner: Morgan Nguyen
Parcel 055-32-01147