Backflow assembly test · Main Street Elementary School
ApprovedFiled Jan 1, 2026 by Cameron Ellery, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Jan 1, 2026
- Assembly type
- RP
- Serial number
- W570892
- Size
- 4
- Test gauge serial
- G-8501
- Gauge calibration date
- Nov 3, 2025
- Check valve 1
- 0.8 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 2.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 055-23-01121
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4072 Orchard Dr
Owner: Lindqvist Holdings LLC
Parcel 055-23-01121