← Backflow review queue
Backflow assembly test · 8102 Meadow Lark Way
ApprovedFiled Jul 25, 2026 by Emerson Calloway, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 25, 2026
- Assembly type
- RP
- Serial number
- W577472
- Size
- 1
- Test gauge serial
- G-9823
- Gauge calibration date
- May 9, 2026
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 055-36-01227
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8102 Meadow Lark Way
Owner: Parker Fairley
Parcel 055-36-01227