← Backflow review queue
Backflow assembly test · 3815 Pine Knoll Ct
ApprovedFiled Jun 13, 2026 by Emerson Calloway, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 13, 2026
- Assembly type
- DC
- Serial number
- B575444
- Size
- 3/4
- Test gauge serial
- G-6443
- Gauge calibration date
- Oct 18, 2025
- Check valve 1
- 5.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 055-10-01004
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3815 Pine Knoll Ct
Owner: Emerson Ellery
Parcel 055-10-01004