Backflow assembly test · 7846 Ridgeview Ln
ApprovedFiled May 3, 2023 by Logan Stroud, Ridge Backflow Testing · filed from phone
Report
- Date of service
- May 3, 2023
- Assembly type
- PVB
- Serial number
- B705192
- Size
- 1
- Test gauge serial
- G-3860
- Gauge calibration date
- Aug 23, 2022
- Check valve 1
- 8.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 059-51-01079
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7846 Ridgeview Ln
Owner: Shawn Okafor
Parcel 059-51-01079