← Backflow review queue
Backflow assembly test · 7882 Spring Branch Ct
ApprovedFiled May 17, 2025 by Riley Calloway, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- May 17, 2025
- Assembly type
- PVB
- Serial number
- W387528
- Size
- 3/4
- Test gauge serial
- G-9525
- Gauge calibration date
- Jan 25, 2025
- Check valve 1
- 5.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 059-90-01217
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7882 Spring Branch Ct
Owner: Parker Danner
Parcel 059-90-01217