← Backflow review queue
Backflow assembly test · Riverside Self Storage
ApprovedFiled Dec 20, 2025 by Logan Stroud, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Dec 20, 2025
- Assembly type
- DC
- Serial number
- K574308
- Size
- 2
- Test gauge serial
- G-8057
- Gauge calibration date
- Jul 12, 2025
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 059-28-01147
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
7647 Turkey Hill Ct
Owner: Ellery Holdings LLC
Parcel 059-28-01147