Placer County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Riverside Apartments

Approved

Filed Sep 4, 2024 by Taylor Ashby, Valley Backflow Testing · filed from phone

Report

Date of service
Sep 4, 2024
Assembly type
RP
Serial number
Z129874
Size
4
Test gauge serial
G-9981
Gauge calibration date
Apr 20, 2024
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 061-92-01277
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

746 Sycamore Trl
Owner: Calloway Holdings LLC
Parcel 061-92-01277