← Backflow review queue
Backflow assembly test · Hilltop Animal Hospital
ApprovedFiled Sep 13, 2026 by Casey Pruitt, Clearwater Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 13, 2026
- Assembly type
- RP
- Serial number
- A171109
- Size
- 1 1/2
- Test gauge serial
- G-6716
- Gauge calibration date
- Jan 6, 2026
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 2.4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 061-51-01287
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
5642 Meadow Lark Way
Owner: Marsh Holdings LLC
Parcel 061-51-01287