ApprovedFiled Jun 12, 2026 by Taylor Ashby, Valley Backflow Testing · filed from phone
Report
- Date of service
- Jun 12, 2026
- Assembly type
- DC
- Serial number
- A629207
- Size
- 1
- Test gauge serial
- G-3924
- Gauge calibration date
- Aug 29, 2025
- Check valve 1
- 4.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 061-33-01099
- Readings in range, no flags
- Result: passing. Next due date resets when approved.