Backflow assembly test · Hilltop Dental
ApprovedFiled Mar 30, 2025 by Reese Calloway, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Mar 30, 2025
- Assembly type
- RP
- Serial number
- K627129
- Size
- 4
- Test gauge serial
- G-1568
- Gauge calibration date
- Jan 8, 2025
- Check valve 1
- 4.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 065-12-01178
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3468 Orchard Ln
Owner: Harlow Holdings LLC
Parcel 065-12-01178