Backflow assembly test · 6055 Turkey Hill Dr
ApprovedFiled Jun 4, 2024 by Morgan Wexler, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 4, 2024
- Assembly type
- RP
- Serial number
- A146809
- Size
- 3/4
- Test gauge serial
- G-1115
- Gauge calibration date
- Apr 19, 2024
- Check valve 1
- 6.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 065-37-01230
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6055 Turkey Hill Dr
Owner: Drew Hollins
Parcel 065-37-01230