Riverside County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5248 Turkey Hill Rd

Approved

Filed Nov 21, 2024 by Blake Harlow, Evergreen Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Nov 21, 2024
Assembly type
DC
Serial number
A138451
Size
3/4
Test gauge serial
G-2412
Gauge calibration date
Sep 24, 2024
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 065-25-01146
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5248 Turkey Hill Rd
Owner: Cameron Ramirez
Parcel 065-25-01146