Backflow assembly test · 7922 Laurel Ct
ApprovedFiled Jan 8, 2025 by Emerson Stroud, Keystone Plumbing & Backflow · filed from phone
Report
- Date of service
- Jan 8, 2025
- Assembly type
- RP
- Serial number
- A983052
- Size
- 1
- Test gauge serial
- G-9464
- Gauge calibration date
- Aug 2, 2024
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 067-46-01291
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.