Backflow assembly test · 8858 Quarry Rd
ApprovedFiled Mar 9, 2026 by Sam Nguyen, Keystone Plumbing & Backflow · filed from phone
Report
- Date of service
- Mar 9, 2026
- Assembly type
- DC
- Serial number
- W121624
- Size
- 1
- Test gauge serial
- G-7730
- Gauge calibration date
- Jan 28, 2026
- Check valve 1
- 7.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 071-18-01135
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.