← Backflow review queue
Backflow assembly test · Golden Car Wash
ApprovedFiled Sep 24, 2026 by Jordan Vance, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 24, 2026
- Assembly type
- RP
- Serial number
- B161604
- Size
- 2
- Test gauge serial
- G-8150
- Gauge calibration date
- May 4, 2026
- Check valve 1
- 9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 071-67-01237
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.