← Backflow review queue
Backflow assembly test · 7079 Stone Gate Rd
ApprovedFiled Mar 9, 2026 by Blake Danner, Summit Backflow Testing · filed from phone
Report
- Date of service
- Mar 9, 2026
- Assembly type
- RP
- Serial number
- W526674
- Size
- 1
- Test gauge serial
- G-4123
- Gauge calibration date
- Jul 10, 2025
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 2.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 071-13-01189
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7079 Stone Gate Rd
Owner: Emerson Fairley
Parcel 071-13-01189