← Backflow review queue
Backflow assembly test · Main Street Self Storage
ApprovedFiled Aug 7, 2024 by Drew Hollins, Summit Backflow Testing · filed from phone
Report
- Date of service
- Aug 7, 2024
- Assembly type
- DC
- Serial number
- A604558
- Size
- 1 1/2
- Test gauge serial
- G-9547
- Gauge calibration date
- Apr 8, 2024
- Check valve 1
- 4.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 071-91-01053
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9120 Laurel Trl
Owner: Stroud Holdings LLC
Parcel 071-91-01053