San Diego County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7371 Meadow Lark Trl

Approved

Filed Nov 26, 2024 by Logan Vance, Ridge Backflow Testing · filed from phone

Report

Date of service
Nov 26, 2024
Assembly type
RP
Serial number
A910179
Size
3/4
Test gauge serial
G-8089
Gauge calibration date
Jul 1, 2024
Check valve 1
8 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 073-57-01304
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7371 Meadow Lark Trl
Owner: Rowan Calloway
Parcel 073-57-01304