Backflow assembly test · 538 Stone Gate Dr
ApprovedFiled Jul 29, 2026 by Logan Vance, Ridge Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jul 29, 2026
- Assembly type
- RP
- Serial number
- Z105533
- Size
- 1
- Test gauge serial
- G-6275
- Gauge calibration date
- Oct 4, 2025
- Check valve 1
- 8.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Relief valve opened at
- 1.6 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 073-74-01199
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
538 Stone Gate Dr
Owner: Riley Brandt
Parcel 073-74-01199