Backflow assembly test · 934 Mill Creek Ln
Sent backFiled Nov 17, 2026 by Logan Vance, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Nov 17, 2026
- Assembly type
- RP
- Serial number
- Z868673
- Size
- 1
- Test gauge serial
- G-9775
- Gauge calibration date
- Sep 18, 2026
- Check valve 1
- 4.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 073-47-01264
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Sent back Please attach the photo of the open tank.