Backflow assembly test · 1423 Pine Knoll Trl
Needs reviewFiled Nov 21, 2026 by Parker Fairley, Heritage Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 21, 2026
- Assembly type
- RP
- Serial number
- A984086
- Size
- 1
- Test gauge serial
- G-5792
- Gauge calibration date
- Mar 23, 2026
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 073-76-01035
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
1423 Pine Knoll Trl
Owner: Jordan Whitcomb
Parcel 073-76-01035