San Diego County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Corner Bakery

Approved

Filed Sep 22, 2026 by Parker Okafor, Valley Backflow Testing · filed from phone

Report

Date of service
Sep 22, 2026
Assembly type
RP
Serial number
A755497
Size
1 1/2
Test gauge serial
G-8128
Gauge calibration date
Oct 9, 2025
Check valve 1
0.2 psid
Check valve 1 closed tight
No
Check valve 2
2.8 psid
Relief valve opened at
2.4 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 073-27-01095
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1470 Stone Gate Trl
Owner: Ramirez Holdings LLC
Parcel 073-27-01095