← Backflow review queue
Backflow assembly test · 3978 Turkey Hill Dr
ApprovedFiled May 26, 2025 by Rowan Kessler, Valley Backflow Testing · filed from phone
Report
- Date of service
- May 26, 2025
- Assembly type
- RP
- Serial number
- B495832
- Size
- 3/4
- Test gauge serial
- G-1480
- Gauge calibration date
- Apr 10, 2025
- Check valve 1
- 7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 073-20-01064
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3978 Turkey Hill Dr
Owner: Parker Stroud
Parcel 073-20-01064