← Backflow review queue
Backflow assembly test · Riverside Grill
ApprovedFiled Oct 8, 2025 by Jordan Wexler, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 8, 2025
- Assembly type
- DC
- Serial number
- A188660
- Size
- 1 1/2
- Test gauge serial
- G-3369
- Gauge calibration date
- Jun 4, 2025
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 075-99-01053
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
5517 Pine Knoll Ct
Owner: Ellery Holdings LLC
Parcel 075-99-01053