Backflow assembly test · Maple Leaf Pizza
ApprovedFiled Mar 29, 2025 by Blake Pruitt, Patriot Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Mar 29, 2025
- Assembly type
- RP
- Serial number
- A270474
- Size
- 2
- Test gauge serial
- G-4813
- Gauge calibration date
- Dec 10, 2024
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 075-50-01074
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.