Backflow assembly test · 5837 Turkey Hill Ct
ApprovedFiled Jul 19, 2025 by Jordan Wexler, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 19, 2025
- Assembly type
- RP
- Serial number
- Z980665
- Size
- 1
- Test gauge serial
- G-9475
- Gauge calibration date
- Mar 4, 2025
- Check valve 1
- 6.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 075-29-01124
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.