← Backflow review queue
Backflow assembly test · 4291 Hickory Rd
ApprovedFiled Jul 12, 2024 by Jordan Wexler, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 12, 2024
- Assembly type
- RP
- Serial number
- B238562
- Size
- 3/4
- Test gauge serial
- G-9809
- Gauge calibration date
- Jun 12, 2024
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 075-58-01031
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
4291 Hickory Rd
Owner: Casey Wexler
Parcel 075-58-01031