← Backflow review queue
Backflow assembly test · 2097 Meadow Lark Way
ApprovedFiled Apr 4, 2025 by Quinn Stroud, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Apr 4, 2025
- Assembly type
- RP
- Serial number
- K574158
- Size
- 1
- Test gauge serial
- G-4822
- Gauge calibration date
- Nov 18, 2024
- Check valve 1
- 6.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 075-46-01337
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2097 Meadow Lark Way
Owner: Jamie Marsh
Parcel 075-46-01337