Backflow assembly test · 7924 Hickory Ln
ApprovedFiled Mar 17, 2025 by Jordan Wexler, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Mar 17, 2025
- Assembly type
- PVB
- Serial number
- A753382
- Size
- 3/4
- Test gauge serial
- G-7649
- Gauge calibration date
- Dec 24, 2024
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 075-99-01209
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7924 Hickory Ln
Owner: Taylor Ashby
Parcel 075-99-01209