← Backflow review queue
Backflow assembly test · 7203 Mill Creek Way
ApprovedFiled Sep 1, 2026 by Blake Hollins, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Sep 1, 2026
- Assembly type
- DC
- Serial number
- K293834
- Size
- 3/4
- Test gauge serial
- G-7197
- Gauge calibration date
- Dec 9, 2025
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 077-55-01090
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7203 Mill Creek Way
Owner: Reese Nguyen
Parcel 077-55-01090