Backflow assembly test · 4048 Mill Creek Ct
ApprovedFiled Mar 8, 2026 by Alex Fairley, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Mar 8, 2026
- Assembly type
- DC
- Serial number
- Z604724
- Size
- 3/4
- Test gauge serial
- G-1800
- Gauge calibration date
- Feb 6, 2026
- Check valve 1
- 4.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 077-25-01353
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.