← Backflow review queue
Backflow assembly test · 1545 Mill Creek Ln
ApprovedFiled Sep 4, 2026 by Parker Okafor, Summit Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Sep 4, 2026
- Assembly type
- DC
- Serial number
- Z813486
- Size
- 3/4
- Test gauge serial
- G-5608
- Gauge calibration date
- Jun 22, 2026
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 079-21-01178
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1545 Mill Creek Ln
Owner: Sam Hollins
Parcel 079-21-01178