Backflow assembly test · 3915 Sycamore Way

Approved

Filed Apr 23, 2026 by Parker Okafor, Summit Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Apr 23, 2026
Assembly type
RP
Serial number
B717669
Size
3/4
Test gauge serial
G-2910
Gauge calibration date
Jul 8, 2025
Check valve 1
0.2 psid
Check valve 1 closed tight
No
Check valve 2
2.7 psid
Relief valve opened at
2.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 079-67-01209
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

3915 Sycamore Way
Owner: Quinn Brandt
Parcel 079-67-01209