Backflow assembly test · 9121 Spring Branch Way

Approved

Filed May 25, 2025 by Parker Okafor, Summit Backflow Testing · filed from phone

Report

Date of service
May 25, 2025
Assembly type
DC
Serial number
K855649
Size
3/4
Test gauge serial
G-1672
Gauge calibration date
Aug 20, 2024
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 079-67-01038
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.