← Backflow review queue
Backflow assembly test · 1064 Cedar Hollow Dr
ApprovedFiled Aug 27, 2025 by Sam Vance, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Aug 27, 2025
- Assembly type
- RP
- Serial number
- W817098
- Size
- 3/4
- Test gauge serial
- G-3227
- Gauge calibration date
- Jun 18, 2025
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 079-61-01289
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
1064 Cedar Hollow Dr
Owner: Avery Wexler
Parcel 079-61-01289