← Backflow review queue
Backflow assembly test · 7551 Cedar Hollow Ln
ApprovedFiled Jul 14, 2025 by Cameron Lindqvist, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 14, 2025
- Assembly type
- RP
- Serial number
- W334499
- Size
- 3/4
- Test gauge serial
- G-7678
- Gauge calibration date
- Apr 5, 2025
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 079-56-01018
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7551 Cedar Hollow Ln
Owner: Blake Kessler
Parcel 079-56-01018