Backflow assembly test · Crossroads Apartments
ApprovedFiled Jan 6, 2025 by Blake Harlow, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Jan 6, 2025
- Assembly type
- RP
- Serial number
- K411212
- Size
- 1
- Test gauge serial
- G-4155
- Gauge calibration date
- Jul 25, 2024
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3 psid
- Relief valve opened at
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 083-69-01243
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.