Backflow assembly test · 3353 Meadow Lark Way
ApprovedFiled Sep 6, 2025 by Parker Vance, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Sep 6, 2025
- Assembly type
- PVB
- Serial number
- B980908
- Size
- 3/4
- Test gauge serial
- G-2132
- Gauge calibration date
- Jan 5, 2025
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 083-93-01327
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.